HomeMy WebLinkAbout2014 - Bayham Water Distribution System2014 ANNUAL
SUMMARY REPORT FOR MUNICIPAL WATER SYSTEMS
Report
This report is a summary of water quality information for the Bayham Water
Distribution System, Water Works # 260004748, published in accordance with
Schedule 22 of the Ontario's Drinking Water Systems Regulation for the reporting
period of January 1, 2014 to December 31, 2014. The Bayham Water Distribution
System is categorized as a Class I, Large Municipal Residential Drinking Water System.
Who gets a copy of the Report:
The owner of the drinking — water system shall ensure that the following receive the
summary report no later than March 31 for the preceding calendar year;
• in the case of a drinking water system owned by a municipality, the members of
the Municipal Council;
• in the case of a drinking water system owned by a municipal service board
established under section 195 of the Municipal Act, 2001, the members of the
municipal service board; or
• in the case of a drinking water system owned by a corporation, the board of
directors of the corporation.
What must the Report contain?
The report must,
(a) list the requirements of the Act, the regulations, the system's approval and any
order that the system failed to meet at any time during the period covered by
the report and specify the duration of the failure; and
(b) for each failure referred to in clause (a), describe the measures that were taken
to correct the failure.
The Bayham Water Distribution System complied with the following Drinking Water
Legislation;
• Safe Drinking Water Act
• O. Reg 170/03, O. Reg 128/04
• System Drinking Water Licence # 061-101
Note: MOE inspection conducted on December 12, 2014 indicates full compliance as
a 100% score was achieved.
What else must the report contain?
The report must also include the following information for the purposes of enabling the
owner of the system to assess the capability of the system to meet existing and planned
uses of the system:
• A summary of the quantities and flow rates of the water supplied during the
period covered by the report;
• A comparison of the summary referred to in paragraph 1 to the rated capacity and
flow rates approved in the system's approval.
Attachments
• 2014 flows
Report Prepared by;
Ed Roloson, CMM III
Water/Wastewater Operations Manager
Overall Responsible Operator ( ORO )
MUNICIPALITY OF BAYHAM MONTHLY WATER CONSUMPTION (m3)
Jan. Feb. March April May June July Aug. Sept. Oct. Nov. Dec. Totals
2014
Pt.Burwell 8941 4387 5638 6137 7406 8711 8587 9883 6241 6932 5052 5182 83,097
avg.daily 288.42 156.68 181.88 204.57 238.9 290.37 277 318.8 208 223.61 168.4 167.16
Vienna 3692 3135 4035 3455 4267 5650 8427 6937 3658 3857 3221 3729 54,063
avg.daily 119.1 111.96 130.16 115.16 137.64 188.33 271.84 223.77 121.93 124.42 107.37 120.29
Lake View 13,457 9055 10,289 10,872 11,292 14,921 21,012 18,957 10,403 12,200 9449 10,223 152,130
avg.daily 434.1 323.39 331.9 362.4 364.29 497.37 677.81 611.51 346.77 393.55 314.97 329.77
2013
Pt.Burwell 5254 8181 5691 5968 7345 8789 10041 11129 9929 9441 8932 8489 99189
avg.daily 169.5 292.2 183.6 198.9 236.9 292.9 323.9 359 331 304.5 297.8 273.8
Vienna 3623 3623 3924 3806 4819 4535 4509 4610 2036 3436 4856 4506 48283
avg.daily 116.9 129.4 126.6 126.9 155.5 151.2 145.5 148.7 68 110.8 161.9 145.4
Lake View 9128 11804 9973 9774 13434 11945 16818 16975 15581 14313 13710 13180 156635
avg.daily 294.5 421.6 321.7 325.8 433.4 398.2 542.5 547.6 519.4 461.7 457 425.2
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
OPTIONAL ANNUAL REPORT TEMPLATE
Drinking-Water System Number: 260004748
Drinking-Water System Name: Bayham Distribution System
Drinking-Water System Owner: The Corporation of the Municipality of Bayham
Drinking-Water System Category: WD Large Municipal Residential
Period being reported: 2014
Complete if your Category is Large Municipal Complete for all other Categories.
Residential or Small Municipal Residential
Does your Drinking-Water System serve Number of Designated Facilities served:
more than 10,000 people? Yes [ ] No [ x
N/A
Is your annual report available to the public Did you provide a copy of your annual
at no charge on a web site on the Internet? report to all Designated Facilities you
Yes [ x ] No [ ] serve?
Yes [ ] No [ ]
Location where Summary Report required
under O. Reg. 170/03 Schedule 22 will be Number of Interested Authorities you
available for inspection. report to:
1 Chatham St. Did you provide a copy of your annual
Port Burwell, Ont. report to all Interested Authorities you
NOJ 1 TO report to for each Designated Facility?
Yes [ ] No [ ]
Note: For the following tables below, additional rows or columns may be added or an
appendix may be attached to the report
List all Drinking-Water Systems (if any), which receive all of their drinking water from
your system:
Drinking Water System Name Drinking Water System Number
N/A
Did you provide a copy of your annual report to all Drinking-Water System owners that
are connected to you and to whom you provide all of its drinking water?
Yes [ ] No [ ]
Drinking Water Systems Regulations Page 1 of 6
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Indicate how you notified system users that your annual report is available, and is free of
charge.
[ x ] Public access/notice via the web
[ x ] Public access/notice via Government Office
[ ] Public access/notice via a newspaper
[ x ] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[x ] Public access/notice via other method_water
bills
Describe your Drinking-Water System
The Bayham water distribution system consists of various size transmission mains and
apparatuses including 81 fire hydrants, 100 main valves and 4 air release and 3 drain
chambers. The location of these are mainly located in the villages of Port Burwell and
Vienna. The estimated service population is less than 2000 with 820 fully metered
service connections. A booster pump station is located on the transmission main to
Vienna. This pump operates when the pressure drops to activate the pump which would
normally occur during fire flows or main line flushing.
List all water treatment chemicals used over this reporting period
No chemicals used as this report is a stand alone distribution system that receives
treated water.
Were any significant expenses incurred to?
[x ] Install required equipment
[x ] Repair required equipment
[ x ] Replace required equipment
Please provide a brief description and a breakdown of monetary expenses incurred
$568,143 --- regulatory operating expenses including purchase of water
Capital costs incurred for 2014 totaled $5,000 for radio water meter head replacements.
Drinking Water Systems Regulations Page 2 of 6
(PIBS 4435e01)February 2008
OntC rio Drinking-Water Systems Regulation O. Reg. 170/03
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe
Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to
Spills Action Centre
Incident Parameter Result Unit of Corrective Action Corrective
Date Measure Action Date
No
adverse
test
results
during
2014
Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03,
during this reporting period.
Number Range of E.Coli Range of Total Number Range of HPC
of Or Fecal Coliform of HPC Results
Samples Results Results Samples (min#)-(max#)
(min#)-(max#) (min#)-(max#)
Raw
Treated
Distribution 156 0 0 156 <10 - 180
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the
period covered by this Annual Report.
Number of Range of Results
Grab (min#)-(max#) NOTE: For continuous
Samples monitors use 8760 as the
Turbidity number of samples.
Chlorine 730 0.20— 1.43 (free)
Fluoride(If the
DWS provides
fluoridation)
NOTE: Record the unit of measure if it is not milligrams per litre.
Drinking Water Systems Regulations Page 3 of 6
(PIBS 4435e01)February 2008
�i Ontario Drinking-Water Systems Regulation 0. Reg. 170/03
Summary of additional testing and sampling carried out in accordance with the
requirement of an approval, order or other legal instrument.
Date of legal instrument Parameter Date Sampled Result Unit of Measure
issued
Summary of Inorganic parameters tested during this reporting period or the most
recent sample results
Parameter Sample Date Result Value Unit of Measure Exceedance
Antimony
Arsenic
Barium
Boron
Cadmium
Chromium
*Lead
Mercury
Selenium
Sodium
Uranium
Fluoride
Nitrite
Nitrate
*only for drinking water systems testing under Schedule 15.2; this includes large municipal non-
residential systems, small municipal non-residential systems,non-municipal seasonal residential
systems, large non-municipal non-residential systems, and small non-municipal non-residential
systems
Drinking Water Systems Regulations Page 4 of 6
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Summary of lead testing under Schedule 15.1 during this reporting period
(applicable to the following drinking water systems; large municipal residential systems, small
municipal residential systems, and non-municipal year-round residential systems)
Number of Range of Number of
Location Type Alkalinity Results
Samples Exceedances
(min#)—(max#)
Plumbing
Distribution 8 pH and 98-129 alk. 0
alkalinity only pH= 7.36-7.75
Summary of Organic parameters sampled during this reporting period or the most
recent sample results
Parameter Sample Result Unit of Exceedance
Date Value Measure
Alachlor
Aldicarb
Aldrin+Dieldrin
Atrazine+N-dealkylated metobolites
Azinphos-methyl
Bendiocarb
Benzene
Benzo(a)pyrene
Bromoxynil
Carbaryl
Carbofuran
Carbon Tetrachloride
Chlordane(Total)
Chlorpyrifos
Cyanazine
Diazinon
Dicamba
1,2-Dichlorobenzene
1,4-Dichlorobenzene
Dichlorodiphenyltrichloroethane(DDT)+
metabolites
1,2-Dichloroethane
1,1-Dichloroethylene
(vinylidene chloride)
Dichloromethane
2-4 Dichlorophenol
2,4-Dichlorophenoxy acetic acid(2,4-D)
Diclofop-methyl
Drinking Water Systems Regulations Page 5 of 6
(PIBS 4435e01)February 2008
�i Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Dimethoate
Dinoseb
Diquat
Diuron
Glyphosate
Heptachlor+Heptachlor Epoxide
Lindane(Total)
Malathion
Methoxychlor
Metolachlor
Metribuzin
Monochlorobenzene
Paraquat
Parathion
Pentachlorophenol
Phorate
Picloram
Polychlorinated Biphenyls(PCB)
Prometryne
Simazine
THM 2014 56.13 ug/L
(NOTE: show latest annual average)
Temephos
Terbufos
Tetrachloroethylene
2,3,4,6-Tetrachlorophenol
Triallate
Trichloroethylene
2,4,6-Trichlorophenol
2,4,5-Trichlorophenoxy acetic acid(2,4,5-T)
Trifluralin
Vinyl Chloride
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed
in Schedule 2 of Ontario Drinking Water Quality Standards.
Parameter Result Value Unit of Measure Date of Sample
THM 59 ug/L Jan.6/14
THM 52 ug/L April 22/14
THM 53 and 50 ug/L July 2/14
THM 85 and 67 ug/L Oct. 6/14
Drinking Water Systems Regulations Page 6 of 6
(PIBS 4435e01)February 2008