HomeMy WebLinkAbout2012 - Bayham Water Distribution System2012 ANNUAL
SUMMARY REPORT FOR MUNICIPAL WATER SYSTEMS
Report
This report is a summary of water quality information for the Bayham Water
Distribution System, Water Works # 260004748, published in accordance with
Schedule 22 of the Ontario's Drinking Water Systems Regulation for the reporting
period of January 1, 2012 to December 31, 2012. The Bayham Water Distribution
System is categorized as a Class I, Large Municipal Residential Drinking Water System.
Who gets a copy of the Report:
The owner of the drinking — water system shall ensure that the following receive the
summary report no later than March 31 for the preceding calendar year;
• in the case of a drinking water system owned by a municipality, the members of
the Municipal Council;
• in the case of a drinking water system owned by a municipal service board
established under section 195 of the Municipal Act, 2001, the members of the
municipal service board; or
• in the case of a drinking water system owned by a corporation, the board of
directors of the corporation.
What must the Report contain?
The report must,
(a) list the requirements of the Act, the regulations, the system's approval and any
order that the system failed to meet at any time during the period covered by
the report and specify the duration of the failure; and
(b) for each failure referred to in clause (a), describe the measures that were taken
to correct the failure.
The Bayham Water Distribution System complied with the following Drinking Water
Legislation;
• Safe Drinking Water Act
• O. Reg 170/03, O. Reg 128/04
• System Drinking Water Licence # 061-101
What else must the report contain?
The report must also include the following information for the purposes of enabling the
owner of the system to assess the capability of the system to meet existing and planned
uses of the system:
• A summary of the quantities and flow rates of the water supplied during the
period covered by the report;
• A comparison of the summary referred to in paragraph 1 to the rated capacity and
flow rates approved in the system's approval.
Attachments
• 2012 flows
Report Prepared by;
Ed Roloson
Water/Wastewater Superintendent
Overall Responsible Operator ( ORO )
MUNICIPALITY OF BAYHAM MONTHLY WATER CONSUMPTION (m3)
Jan. Feb. March April May June July Aug. Sept. Oct. Nov. Dec. Totals
2012
Pt.Burwell 5610 5305 6381 6096 8203 7994 12589 10204 8367 7592 5801 5766 89908
avg.daily 180.97 189.46 205.84 203.2 264.61 266.47 406.1 329.16 278.9 244.9 193.37 186
Vienna 3367 3492 4335 4859 5045 4222 5468 4407 4199 4131 3558 3625 50708
avg.daily 108.61 124.71 139.84 161.97 162.74 140.73 176.38 142.16 139.67 133.26 118.6 116.94
Lake View 9503 9007 11070 11143 13703 12705 18745 15132 12862 12190 9516 9391 144967
avg.daily 306.55 321.68 357.1 371.43 442.03 423.5 604.68 488.13 428.73 393.22 317.2 302.94
2011
Pt.Burwell 8884 7161 6897 5974 7725 7870 11445 10895 8112 7525 5936 6616 95040
avg.daily 236.71 256.5 220.87 200.06 247.64 272.7 412.16 286.42 270.4 250.83 191.48 213.42
Vienna 3445 3454 3461 3650 3979 4096 4952 4660 3271 3595 3615 4000 46178
avg.daily 93.19 123.5 110.84 123.03 127.74 140.67 164.03 137.52 109 119.82 116.61 129.03
Lake View 12706 10947 10769 11413 11777 12075 16986 16366 11886 11395 9699 10749 146768
avg.daily 403.29 373.89 347.39 380.43 379.9 411.13 581.64 473.77 396.2 379.83 312.87 346.74
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
OPTIONAL ANNUAL REPORT TEMPLATE
Drinking-Water System Number: 260004748
Drinking-Water System Name: Bayham Distribution System
Drinking-Water System Owner: The Corporation of the Municipality of Bayham
Drinking-Water System Category: WD Large Municipal Residential
Period being reported: 2012
Complete if your Category is Large Municipal Complete for all other Categories.
Residential or Small Municipal Residential
Does your Drinking-Water System serve Number of Designated Facilities served:
more than 10,000 people? Yes [ ] No [ x
N/A
Is your annual report available to the public Did you provide a copy of your annual
at no charge on a web site on the Internet? report to all Designated Facilities you
Yes [ x ] No [ ] serve?
Yes [ ] No [ ]
Location where Summary Report required
under O. Reg. 170/03 Schedule 22 will be Number of Interested Authorities you
available for inspection. report to:
1 Chatham St. Did you provide a copy of your annual
Port Burwell, Ont. report to all Interested Authorities you
NOJ 1 TO report to for each Designated Facility?
Yes [ ] No [ ]
Note: For the following tables below, additional rows or columns may be added or an
appendix may be attached to the report
List all Drinking-Water Systems (if any), which receive all of their drinking water from
your system:
Drinking Water System Name Drinking Water System Number
N/A
Did you provide a copy of your annual report to all Drinking-Water System owners that
are connected to you and to whom you provide all of its drinking water?
Yes [ ] No [ ]
Drinking Water Systems Regulations Page 1 of 5
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Indicate how you notified system users that your annual report is available, and is free of
charge.
[ x ] Public access/notice via the web
[ x ] Public access/notice via Government Office
[ ] Public access/notice via a newspaper
[ x ] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[x ] Public access/notice via other method_water
bills
Describe your Drinking-Water System
The Bayham water distribution system consists of various size transmission mains and
apparatuses including 81 fire hydrants, 100 main valves and 4 air release and 3 drain
chambers. The location of these are mainly located in the villages of Port Burwell and
Vienna. The estimated service population is less than 2000 with 820 fully metered
service connections. A booster pump station is located on the transmission main to
Vienna. This pump operates when the pressure drops to activate the pump which would
normally occur during fire flows or main line flushing.
List all water treatment chemicals used over this reporting period
No chemicals used as this report is for a distribution system that receives treated water.
Were any significant expenses incurred to?
[x ] Install required equipment
[x ] Repair required equipment
[ x ] Replace required equipment
Please provide a brief description and a breakdown of monetary expenses incurred
$596,210 --- regulatory operating expenses including purchase of water
No capital costs incurred for 2012.
Drinking Water Systems Regulations Page 2 of 5
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe
Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to
Spills Action Centre
Incident Parameter Result Unit of Corrective Action Corrective
Date Measure Action Date
No
adverse
test
results
during
2012
Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03,
during this reporting period.
Number Range of E.Coli Range of Total Number Range of HPC
of Or Fecal Coliform of HPC Results
Samples Results Results Samples (min#)-(max#)
(min#)-(max#) (min#)-(max#)
Raw
Treated
Distribution 156 0 0 156 <10 - 120
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the
period covered by this Annual Report.
Number of Range of Results
Grab (min#)-(max#) NOTE: For continuous
Samples monitors use 8760 as the
Turbidity number of samples.
Chlorine 730 _ 0.15—2.06 (free)
Fluoride(If the
DWS provides
fluoridation)
NOTE: Record the unit of measure if it is not milligrams per litre.
Summary of additional testing and sampling carried out in accordance with the
requirement of an approval, order or other legal instrument.
Date of legal instrument Parameter Date Sampled Result Unit of Measure
issued
Drinking Water Systems Regulations Page 3 of 5
(PIBS 4435e01)February 2008
(-
lir-7
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Summary of Inorganic parameters tested during this reporting period or the most
recent sample results
Parameter Sample Date Result Value Unit of Measure Exceedance
Antimony
Arsenic
Barium
Boron
Cadmium
Chromium
*Lead
Mercury
Selenium
Sodium
Uranium
Fluoride
Nitrite
Nitrate
*only for drinking water systems testing under Schedule 15.2;this includes large municipal non-
residential systems, small municipal non-residential systems,non-municipal seasonal residential
systems, large non-municipal non-residential systems, and small non-municipal non-residential
systems
Summary of lead testing under Schedule 15.1 during this reporting period
(applicable to the following drinking water systems; large municipal residential systems,small
municipal residential systems, and non-municipal year-round residential systems)
Number of Range of Number of
Location Type Alkalinity Results
Samples Exceedances
(min#)—(max#)
Plumbing
Distribution 8 pH and 76-83 alk. 0
alkalinity only pH= 7.30-7.57
Summary of Organic parameters sampled during this reporting period or the most
recent sample results
Parameter Sample Result Unit of Exceedance
Date Value Measure
Alachlor
Aldicarb
Aldrin+Dieldrin
Drinking Water Systems Regulations Page 4 of 5
(PIBS 4435e01)February 2008
(-
�i Ontario Drinking-Water Systems Regulation 0. Reg. 170/03
Atrazine+N-dealkylated metobolites
Azinphos-methyl
Bendiocarb
Benzene
Benzo(a)pyrene
Bromoxynil
Carbaryl
Carbofuran
Carbon Tetrachloride
Chlordane(Total)
Chlorpyrifos
Cyanazine
Diazinon
Dicamba
1,2-Dichlorobenzene
1,4-Dichlorobenzene
Dichlorodiphenyltrichloroethane(DDT)+
metabolites
1,2-Dichloroethane
1,1-Dichloroethylene
(vinylidene chloride)
Dichloromethane
2-4 Dichlorophenol
2,4-Dichlorophenoxy acetic acid(2,4-D)
Diclofop-methyl
Dimethoate
Dinoseb
Diquat
Diuron
Glyphosate
Heptachlor+Heptachlor Epoxide
Lindane(Total)
Malathion
Methoxychlor
Metolachlor
Metribuzin
Monochlorobenzene
Paraquat
Parathion
Pentachlorophenol
Phorate
Picloram
Polychlorinated Biphenyls(PCB)
Prometryne
Simazine
Drinking Water Systems Regulations Page 5 of 5
(PIBS 4435e01)February 2008
�r�
,iX- Ontario Drinking-Water Systems Regulation O. Reg. 170/03
THM 2012 59.25 ug/L
(NOTE: show latest annual average)
Temephos
Terbufos
Tetrachloroethylene
2,3,4,6-Tetrachlorophenol
Triallate
Trichloroethylene
2,4,6-Trichlorophenol
2,4,5-Trichlorophenoxy acetic acid(2,4,5-T)
Trifluralin
Vinyl Chloride
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed
in Schedule 2 of Ontario Drinking Water Quality Standards.
Parameter Result Value Unit of Measure Date of Sample
THM 54 ug/L Jan. 19/12
THM 58 ug/L July 11/12
THM 93 and 96 ug/L Oct. 9/12
Drinking Water Systems Regulations Page 6 of 5
(PIBS 4435e01)February 2008