HomeMy WebLinkAbout2009 - Bayham Water Distribution System 2009 ANNUAL
SUMMARY REPORT FOR MUNICIPAL WATER SYSTEMS
Report
This report is a summary of water quality information for the Bayham Water Distribution
System, Water Works #260004748,published in accordance with Schedule 22 of the
Ontario's Drinking Water Systems Regulation for the reporting period of January 1, 2009
to December 31, 2009. The Bayham Water Distribution System is categorized as a Class
I, Large Municipal Residential Drinking Water System.
Who gets a copy of the Report:
The owner of the drinking—water system shall ensure that the following receive the
summary report no later than March 31 for the preceding calendar year;
• in the case of a drinking water system owned by a municipality, the members of
the Municipal Council;
• in the case of a drinking water system owned by a municipal service board
established under section 195 of the Municipal Act, 2001, the members of the
municipal service board; or
• in the case of a drinking water system owned by a corporation, the board of
directors of the corporation.
What must the Report contain?
The report must,
(a) list the requirements of the Act, the regulations, the system's approval and any
order that the system failed to meet at any time during the period covered by
the report and specify the duration of the failure; and
(b) for each failure referred to in clause (a), describe the measures that were taken
to correct the failure.
The Bayham Water Distribution System complied with the following Drinking Water
Legislation;
• Safe Drinking Water Act
• O. Reg 170/03, O. Reg 128/04
• System Certificate of Approval# 1788-5SHLD5
• Provincial Officer's Order# (N/A)
What else must the report contain?
The report must also include the following information for the purposes of enabling the
owner of the system to assess the capability of the system to meet existing and planned
uses of the system:
• A summary of the quantities and flow rates of the water supplied during the
period covered by the report;
• A comparison of the summary referred to in paragraph 1 to the rated capacity and
flow rates approved in the system's approval.
Attachments
• 2009 flows
• O. Reg 170/03, 2009 Annual Report Part III, Form 2
Report Prepared by;
Ed Roloson
Water/Wastewater Superintendent
Overall Responsible Operator (ORO)
MUNICIPALITY OF BAYHAM MONTHLY WATER CONSUMPTION (m3)
Jan. Feb. March April May June July Aug. Sept. Oct. Nov. Dec. Totals
2009
Pt.Burwell 7730 6495 7410 7690 9780 9770 9770 10995 12030 0 0 7740 89410
avg.daily 249.35 231.96 239.03 256.33 315.48 315.16 315.16 354.68 401 0 0
Vienna 4405 1920 290 4760 930 0 0 0 0 0 0 7973 12305
avg.daily 142.1 68.57 9.35 158.67 30 0 0 0 0 0 0
Lake View 12773 11098 12808 13216 16108 15098 16722 17619 15404 14102 11691 11516 168155
avg.daily 412.03 396.36 413.16 450.53 519.61 487 539.42 568.35 513.47 455 389.7 371.48
2008
Pt.Burwell 6655 5275 8290 8660 10490 10675 13750 14735 10320 10300 7915 10390 117455
avg.daily 214.68 181.9 267.42 288.67 338.38 355.83 443.55 475.32 344 332.26 263.83 335.16
Vienna 895 2815 3885 4525 4930 4500 5680 5800 4560 4565 4040 4685 50880
avg.daily 28.87 97.07 125.32 150.83 159.03 150 183.22 187.1 152 147.26 134.67 151.13
Lake View 11812 10985 12634 13848 16494 15738 19902 20965 15494 15562 12606 15311 181351
avg.daily 381 378.79 407.55 461.6 532.06 524.6 642 676.29 516.47 502 420.2 493.9
2007
Pt.Burwell 8640 7435 7750 7190 9585 12200 12690 13160 8155 8824 7211 6685 109525
avg.daily 278.71 265.54 250 239.67 309.19 406.67 409.35 424.52 271.83 284.64 240.37 215.65
Vienna 8185 1940 2290 1915 3075 5090 4255 4005 2630 1575 780 715 36455
avg.daily 264 69.28 73.87 63.83 99.19 169.67 137.25 129.19 87.67 50.81 26 23.1
Lake View 20941 12978 13797 13204 16109 19816 19287 19916 13602 15214 13163 11568 189595
avg.daily 675.52 463.5 445.1 440.13 519.64 660.53 622.16 642.45 438.77 490.77 438.77 373.16
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
OPTIONAL ANNUAL REPORT TEMPLATE
Drinking-Water System Number: 260004748
Drinking-Water System Name: Bayham Distribution System
Drinking-Water System Owner: The Corporation of the Municipality of Bayham
Drinking-Water System Category: WD Large Municipal Residential
Period being reported: 2009
Complete if your Category is Large Municipal Complete for all other Categories.
Residential or Small Municipal Residential
Does your Drinking-Water System serve Number of Designated Facilities served:
more than 10,000 people? Yes [ ] No [ x
N/A
Is your annual report available to the public Did you provide a copy of your annual
at no charge on a web site on the Internet? report to all Designated Facilities you
Yes [ x ] No [ ] serve?
Yes [ ] No [ ]
Location where Summary Report required
under O. Reg. 170/03 Schedule 22 will be Number of Interested Authorities you
available for inspection. report to:
1 Chatham St. Did you provide a copy of your annual
Port Burwell, Ont. report to all Interested Authorities you
NOJ 1 TO report to for each Designated Facility?
Yes [ ] No [ ]
Note: For the following tables below, additional rows or columns may be added or an
appendix may be attached to the report
List all Drinking-Water Systems (if any), which receive all of their drinking water from
your system:
Drinking Water System Name Drinking Water System Number
N/A
Did you provide a copy of your annual report to all Drinking-Water System owners that
are connected to you and to whom you provide all of its drinking water?
Yes [ ] No [ ]
Drinking Water Systems Regulations Page 1 of 5
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Indicate how you notified system users that your annual report is available, and is free of
charge.
[ ] Public access/notice via the web
[ x ] Public access/notice via Government Office
[ ] Public access/notice via a newspaper
[ x ] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[x ] Public access/notice via other method_water
bills
Describe your Drinking-Water System
The Bayham water distribution system consists of various size transmission mains and
apparatuses including 81 fire hydrants, 100 main valves and 3 air release and 3 drain
chambers. The location of these are mainly located in the villages of Port Burwell and
Vienna. The estimated service population is less than 2000 with 765 fully metered
service connections. A booster pump station is located on the transmission main to
Vienna. This pump operates when the pressure drops to activate the pump which would
normally occur during fire flows or main line flushing.
List all water treatment chemicals used over this reporting period
No chemicals used as this report is for a distribution system that receives treated water.
Were any significant expenses incurred to?
[x ] Install required equipment
[x ] Repair required equipment
[ x ] Replace required equipment
Please provide a brief description and a breakdown of monetary expenses incurred
The Bayham water distribution system has undergone capital repairs through
infrastructure grants during 2009 that include replacement of service saddles, main
stops, curb stops, main valves, and fire hydrants. The completion of the said project will
take place in the summer of 2010. The estimated total cost is $2 million.
Drinking Water Systems Regulations Page 2 of 5
(PIBS 4435e01)February 2008
OntC rio Drinking-Water Systems Regulation O. Reg. 170/03
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe
Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to
Spills Action Centre
Incident Parameter Result Unit of Corrective Action Corrective
Date Measure Action Date
No
adverse
test
results
during
2009
Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03,
during this reporting period.
Number Range of E.Coli Range of Total Number Range of HPC
of Or Fecal Coliform of HPC Results
Samples Results Results Samples (min#)-(max#)
(min#)-(max#) (min#)-(max#)
Raw
Treated
Distribution 156 0 0 156 <10 - 210
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the
period covered by this Annual Report.
Number of Range of Results
Grab (min#)-(max#) NOTE: For continuous
Samples monitors use 8760 as the
Turbidity number of samples.
Chlorine 730 0.20— 1.80 (free)
Fluoride(If the
DWS provides
fluoridation)
NOTE: Record the unit of measure if it is not milligrams per litre.
Summary of additional testing and sampling carried out in accordance with the
requirement of an approval, order or other legal instrument.
Drinking Water Systems Regulations Page 3 of 5
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Date of legal instrument Parameter Date Sampled Result Unit of Measure
issued
Summary of Inorganic parameters tested during this reporting period or the most
recent sample results
Parameter Sample Date Result Value Unit of Measure Exceedance
Antimony
Arsenic
Barium
Boron
Cadmium
Chromium
*Lead
Mercury
Selenium
Sodium
Uranium
Fluoride
Nitrite
Nitrate
*only for drinking water systems testing under Schedule 15.2; this includes large municipal non-
residential systems, small municipal non-residential systems,non-municipal seasonal residential
systems, large non-municipal non-residential systems, and small non-municipal non-residential
systems
Summary of lead testing under Schedule 15.1 during this reporting period
(applicable to the following drinking water systems; large municipal residential systems, small
municipal residential systems, and non-municipal year-round residential systems)
Range of Lead
Location Type Number of Number of
Results
Samples Exceedances
(min#)—(max#)
Plumbing 48 ND— 1.72 0
Distribution 8 ND— 1.35 0
Summary of Organic parameters sampled during this reporting period or the most
recent sample results
Parameter Sample Result Unit of Exceedance
Date Value Measure
Alachlor
Drinking Water Systems Regulations Page 4 of 5
(PIBS 4435e01)February 2008
(-
�i Ontario Drinking-Water Systems Regulation 0. Reg. 170/03
Aldicarb 1
Aldrin+Dieldrin
Atrazine+N-dealkylated metobolites
Azinphos-methyl
Bendiocarb
Benzene
Benzo(a)pyrene
Bromoxynil
Carbaryl
Carbofuran
Carbon Tetrachloride
Chlordane(Total)
Chlorpyrifos
Cyanazine
Diazinon
Dicamba
1,2-Dichlorobenzene
1,4-Dichlorobenzene
Dichlorodiphenyltrichloroethane(DDT)+
metabolites
1,2-Dichloroethane
1,1-Dichloroethylene
(vinylidene chloride)
Dichloromethane
2-4 Dichlorophenol
2,4-Dichlorophenoxy acetic acid(2,4-D)
Diclofop-methyl
Dimethoate
Dinoseb
Diquat
Diuron
Glyphosate
Heptachlor+Heptachlor Epoxide
Lindane(Total)
Malathion
Methoxychlor
Metolachlor
Metribuzin
Monochlorobenzene
Paraquat
Parathion
Pentachlorophenol
Phorate
Picloram
Polychlorinated Biphenyls(PCB)
Drinking Water Systems Regulations Page 5 of 5
(PIBS 4435e01)February 2008
(-
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Prometryne
Simazine
THM 0.045 mg/L
(NOTE: show latest annual average)
Temephos
Terbufos
Tetrachloroethylene
2,3,4,6-Tetrachlorophenol
Triallate
Trichloroethylene
2,4,6-Trichlorophenol
2,4,5-Trichlorophenoxy acetic acid(2,4,5-T)
Trifluralin
Vinyl Chloride
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed
in Schedule 2 of Ontario Drinking Water Quality Standards.
Parameter Result Value Unit of Measure Date of Sample
Drinking Water Systems Regulations Page 6 of 5
(PIGS 4435e01)February 2008