HomeMy WebLinkAbout2010 - Richmond Community Water System Ontario Drinking-Water Systems Regulation O. Reg. 170/03
OPTIONAL ANNUAL REPORT TEMPLATE
Drinking-Water System Number: 260074854
Drinking-Water System Name: Richmond Community Water Inc.
Drinking-Water System Owner: Richmond Community Water Inc.
Drinking-Water System Category: Non-Municipal Year Round Residential
Period being reported: 2010
Complete if your Category is Large Municipal Complete for all other Categories.
Residential or Small Municipal Residential
Does your Drinking-Water System serve Number of Designated Facilities served:
more than 10,000 people? Yes [ ] No [ x
N/A
Is your annual report available to the public Did you provide a copy of your annual
at no charge on a web site on the Internet? report to all Designated Facilities you
Yes [ ] No [ x ] serve?
Yes [ ] No [x ]
Location where Summary Report required
under O. Reg. 170/03 Schedule 22 will be Number of Interested Authorities you
available for inspection. report to: N/A
Bayham Wastewater Treatment Plant Did you provide a copy of your annual
1 Chatham St. report to all Interested Authorities you
Port Burwell,ON report to for each Designated Facility?
519-874-4761 Yes [ ] No [x
Note: For the following tables below, additional rows or columns may be added or an
appendix may be attached to the report
List all Drinking-Water Systems (if any), which receive all of their drinking water from
your system:
Drinking Water System Name Drinking Water System Number
Did you provide a copy of your annual report to all Drinking-Water System owners that
are connected to you and to whom you provide all of its drinking water?
Yes [ x ] No [ ]
Drinking Water Systems Regulations Page 1 of 5
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Indicate how you notified system users that your annual report is available, and is free of
charge.
[x ] Public access/notice via the web
[x ] Public access/notice via Government Office
[ ] Public access/notice via a newspaper
[x] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[x] Public access/notice via other method ---water bills
Describe your Drinking-Water System
The Richmond Well Supply consists of two artesian and surface water collection
systems located in a ravine. Raw water is collected in an excavated area into pre-cast
concrete containments lined with filter cloth and clear stone. The raw water flows via
gravity to the lower level of the ravine and is pumped to treatment pumphouse.
Treatment consists of canister filtration, ultraviolet irradiation (UV) and chlorination.
Two distribution lines feed 50 residents and 1 church.
The water system is classified as non-municipal year round residential. The said system
is owned by Richmond Community Water Inc. and has been operated by the
Municipality of Bayham from March 1 —December 31, 2010.
List all water treatment chemicals used over this reporting period
Sodium Hypochlorite ( 12% )
Were any significant expenses incurred to?
[x] Install required equipment
[ x ] Repair required equipment
[ x ] Replace required equipment
Please provide a brief description and a breakdown of monetary expenses incurred
$33,500 --- engineering and drilling of a new well.
$1,500 --- replacement of UV sleeves and bulbs.
$900 ---pump replacement
Drinking Water Systems Regulations Page 2 of 5
(PIBS 4435e01)February 2008
OntC rio Drinking-Water Systems Regulation O. Reg. 170/03
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe
Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to
Spills Action Centre
Incident Parameter Result Unit of Corrective Action Corrective
Date Measure Action Date
May 14/10 Turbidity 9.36 NTU DWA May 20/10
June 6/10 turbidity 1.08 NTU DWA June 15/10
Oct.25/10 nitrates 10.2 mg/L resample Oct. 29/10
10.3
Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03,
during this reporting period.
Number Range of E.Coli Range of Total Number Range of HPC
of Or Fecal Coliform of HPC Results
Samples Results Results Samples (min#)-(max#)
(min#)-(max#) (min#)-(max#)
Raw 24 0 - 22 32 - 340 0
Treated
Distribution 104 0 -0 0-0 104 0 - 110
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the
period covered by this Annual Report.
Number of Range of Results
Grab (min#)-(max#) NOTE: For continuous
Samples monitors use 8760 as the
Turbidity 730 0.08—9.36 number of samples.
Chlorine 938 0.45—3.0 (free)
Fluoride(If the
DWS provides
fluoridation)
NOTE: Record the unit of measure if it is not milligrams per litre.
Summary of additional testing and sampling carried out in accordance with the
requirement of an approval, order or other legal instrument.
Date of legal instrument Parameter Date Sampled Result Unit of Measure
issued
Drinking Water Systems Regulations Page 3 of 5
(PIBS 4435e01)February 2008
Ontario Drinking-Water Systems Regulation O. Reg. 170/03
Summary of Inorganic parameters tested during this reporting period or the most
recent sample results
Parameter Sample Date Result Value Unit of Measure Exceedance
Antimony Aug.24/07 0.2 ug/L
Arsenic Aug. 24/07 0.3 ug/L
Barium Aug.24/07 40.7 ug/L
Boron Aug.24/07 33 ug/L
Cadmium Aug.24/07 0.06 ug/L
Chromium Aug.24/07 2.2 ug/L
*Lead See below
Mercury Aug.24/07 0.02 ug/L
Selenium Aug.24/07 1 ug/L
Sodium Aug.23/07 40.1 mg/L yes
Uranium Aug.24/07 0.16 ug/L
Fluoride Aug.27/07 0.06 mg/L
Nitrite Oct.25/10 0.005 mg/L
Nitrate Oct.25/10 9.73 & 9.78 mg/L
*only for drinking water systems testing under Schedule 15.2; this includes large municipal non-
residential systems, small municipal non-residential systems,non-municipal seasonal residential
systems, large non-municipal non-residential systems, and small non-municipal non-residential
systems
Summary of lead testing under Schedule 15.1 during this reporting period
(applicable to the following drinking water systems; large municipal residential systems, small
municipal residential systems, and non-municipal year-round residential systems)
Range of Lead
Location Type Number of Number of
Results
Samples Exceedances
(min#)-(max#)
Plumbing 22 0.3-2.9 ug/L 0
Distribution 4 0.17-0.50 ug/L 0
Summary of Organic parameters sampled during this reporting period or the most
recent sample results
Parameter Sample Result Unit of Exceedance
Date Value Measure
Alachlor Aug.28/07 0.11 ug/L
Aldicarb Aug.28/07 0.30 ug/L
Aldrin+Dieldrin Aug.28/07 0.067 ug/L
Atrazine+N-dealkylated metobolites Aug.28/07 0.12 ug/L
Azinphos-methyl Aug.28/07 0.21 ug/L
Bendiocarb Aug.28/07 0.13 ug/L
Benzene Aug.22/07 0.37 ug/L
Benzo(a)pyrene Aug.27/07 0.004 ug/L
Bromoxynil Aug.23/07 0.33 ug/L
Carbaryl Aug.28/07 0.16 ug/L
Drinking Water Systems Regulations Page 4 of 5
(PIBS 4435e01)February 2008
(-
7
ii Ontario Drinking-Water Systems Regulation 0. Reg. 170/03
Carbofuran Aug.28/07 0.37 ug/L
Carbon Tetrachloride Aug.28/07 0.41 ug/L
Chlordane(Total) Aug.28/07 0.11 ug/L
Chlorpyrifos Aug.28/07 0.18 ug/L
Cyanazine Aug.28/07 0.18 ug/L
Diazinon Aug.28/07 0.081 ug/L
Dicamba Aug.28/07 0.20 ug/L
1,2-Dichlorobenzene Aug.28/07 10.50 ug/L
1,4-Dichlorobenzene Aug.28/07 0.21 ug/L
Dichlorodiphenyltrichloroethane(DDT)+ Aug.28/07 0.14 ug/L
metabolites
1,2-Dichloroethane Aug.28/07 0.43 ug/L
1,1-Dichloroethylene Aug.28/07 0.41 ug/L
(vinylidene chloride)
Dichloromethane Aug.28/07 0.43 ug/L
2-4 Dichlorophenol Aug.28/07 0.15 ug/L
2,4-Dichlorophenoxy acetic acid(2,4-D) Aug.28/07 0.19 ug/L
Diclofop-methyl Aug.28/07 0.40 ug/L
Dimethoate Aug.28/07 0.12 ug/L
Dinoseb Aug.28/07 0.36 g/L
Diquat Aug.28/07 1.0 ug/L
Diuron Aug.28/07 0.087 ug/L
Glyphosate Aug.28/07 6.0 ug/L
Heptachlor+Heptachlor Epoxide Aug.28/07 0.11 ug/L
Lindane(Total) Aug.28/07 0.056 ug/L
Malathion Aug.28/07 0.091 ug/L
Methoxychlor Aug.28/07 0.14 ug/L
Metolachlor Aug.28/07 0.092 ug/L
Metribuzin Aug.28/07 0.12 ug/L
Monochlorobenzene Aug.28/07 0.58 ug/L
Paraquat Aug.28/07 1.0 ug/L
Parathion Aug.28/07 0.18 ug/L
Pentachlorophenol Aug.28/07 0.15 ug/L
Phorate Aug.28/07 0.11 ug/L
Picloram Aug.28/07 0.25 ug/L
Polychlorinated Biphenyls(PCB) Aug.28/07 0.04 ug/L
Prometryne Aug.28/07 0.23 ug/L
Simazine Aug.28/07 0.15 ug/L
THM 2010 East ug/L
(NOTE: show latest annual average) 11.1
West
13.2
Temephos Aug.28/07 0.31 ug/L
Terbufos Aug.28/07 0.12 ug/L
Tetrachloroethylene Aug.28/07 0.45 ug/L
Drinking Water Systems Regulations Page 5 of 5
(PIGS 4435e01)February 2008
(-
�i Ontario Drinking-Water Systems Regulation O. Reg. 170/03
2,3,4,6-Tetrachlorophenol Aug.28/07 0.14 ug/L
Triallate Aug.28/07 0.10 ug/L
Trichloroethylene Aug.28/07 0.38 ug/L
2,4,6-Trichlorophenol Aug.28/07 0.25 ug/L
2,4,5-Trichlorophenoxy acetic acid(2,4,5-T) Aug.28/07 0.22 ug/L
Trifluralin Aug.28/07 0.12 ug/L
Vinyl Chloride Aug.28/07 0.17 ug/L
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed
in Schedule 2 of Ontario Drinking Water Quality Standards.
Parameter Result Value Unit of Measure Date of Sample
Drinking Water Systems Regulations Page 6 of 5
(PIBS 4435e01)February 2008