HomeMy WebLinkAbout2019 - Richmond Community Water System
Drinking-Water Systems Regulation O. Reg. 170/03
Drinking Water Systems Regulations
(PIBS 4435e01) February 2008 Page 1 of 6
OPTIONAL ANNUAL REPORT TEMPLATE
Drinking-Water System Number: 260074854
Drinking-Water System Name: Richmond Community Water Inc.
Drinking-Water System Owner: The Corporation of the Municipality of Bayham
Drinking-Water System Category: Small Munici pal Year Round Residential
Period being reported: 2019
Complete if your Category is Large Municipal
Residential or Small Municipal Residential
Does your Drinking-Water System serve
more than 10,000 people? Yes [ ] No [ x ]
Is your annual report available to the public
at no charge on a web site on the Internet?
Yes [ x ] No [ ]
Location where Summary Report required
under O. Reg. 170/03 Schedule 22 will be
available for inspection.
Complete for all other Categories.
Number of Designated Facilities served:
Did you provide a copy of your annual
report to all Designated Facilities you
serve?
Yes [ ] No [x ]
Number of Interested Authorities you
report to:
Did you provide a copy of your annual
report to all Interested Authorities you
report to for each Designated Facility?
Yes [ ] No [ x ]
Note: For the following tables below, additional rows or columns may be added or an
appendix may be attached to the report
List all Drinking-Water Systems (if any), which receive all of their drinking water from
your system:
Drinking Water System Name Drinking Water System Number
N/A
Did you provide a copy of your annual report to all Drinking-Water System owners that
are connected to you and to whom you provide all of its drinking water?
Yes [ ] No [ ]
Bayham Wastewater Treatment Plant
1 Chatham St.
Port Burwell,ON
519-874-4761
N/A
N/A
Drinking-Water Systems Regulation O. Reg. 170/03
Drinking Water Systems Regulations
(PIBS 4435e01) February 2008 Page 2 of 6
Indicate how you notified system users that your annual report is available, and is free of
charge.
[x ] Public access/notice via the web
[x ] Public access/notice via Government Office
[ ] Public access/notice via a newspaper
[x] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[ x] Public access/notice via other method --- water bills
_______________________________________
Describe your Drinking-Water System
The community is serviced by two drilled overburden wells and treatment equipment
upgrades including raw water softeners, nitrate filters, pre and post chlorination, post
filtration, uv disinfection, on-line continuous monitoring equipment including nitrate,
turbidity and chlorine. The system is monitored and alarmed by a computerized
SCADA system.
List all water treatment chemicals used over this reporting period
Sodium Hypochlorite ( 12% )
Were any significant expenses incurred to?
[ x ] Install required equipment
[ x ] Repair required equipment
[ x ] Replace required equipment
Please provide a brief description and a breakdown of monetary expenses incurred
$64,191 – operating expenses
$21,000 – capital expenses including replacement of 2 well pumps and well casing
videos as well as water financial plan
Drinking-Water Systems Regulation O. Reg. 170/03
Drinking Water Systems Regulations
(PIBS 4435e01) February 2008 Page 3 of 6
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe
Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to
Spills Action Centre
Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03,
during this reporting period.
Number
of
Samples
Range of E.Coli
Or Fecal
Results
(min #)-(ma x #)
Range of Total
Coliform
Results
(min #)-(max #)
Number
of HPC
Samples
Range of HPC
Results
(min #)-(max #)
Raw 24 0 0 0
Treated
Distribution 114 0 0 - 23 114 >10 - 60
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the
period covered by this Annual Report.
Number of
Grab
Samples
Range of Results
(min #)-(max #)
Turbidity 8760 0.00 –2.00 (equip
cal)
Chlorine 8760 0.00(equip cal) –
2.87 (free)
Fluoride (If the
DWS provides
NOTE: Record the unit of measure if it is not milligrams per litre.
Incident
Date
Parameter Result Unit of
Measure
Corrective Action Corrective
Action Date
Jan.22/19 Sodium 95.6 mg/L Ongoing DWA
by MOH
Jan 29/19
April 2/19 Nitrate 10.3 mg/L Resampled April 16/19
July 9/19 Total Coliforms 4 C/ 100
mL
Resampled July 15/19
July 30/19 Total Coliforms 23 C/ 100
mL
Resampled Aug 6/19
NOTE: For continuous
monitors use 8760 as the
number of samples.
Drinking-Water Systems Regulation O. Reg. 170/03
Drinking Water Systems Regulations
(PIBS 4435e01) February 2008 Page 4 of 6
Summary of additional testing and sampling carried out in accordance with the
requirement of an approval, order or other legal instrument.
Date of legal instrument
issued
Parameter Date Sampled Result Unit of Measure
Summary of Inorganic parameters tested during this reporting period or the most
recent sample results
Parameter Sample Date Result Value Unit of Measure Exceedance
Antimony Jan.19/15 0.05 ug/L
Arsenic Jan.19/15 0.2 ug/L
Barium Jan.19/15 31.3 ug/L
Boron Jan.19/15 26.7 ug/L
Cadmium Jan.19/15 0.008 ug/L
Chromium Jan.19/15 0.13 ug/L
*Lead See below
Mercury Jan.19/15 0.01 ug/L
Selenium Jan.19/15 1 ug/L
Sodium Jan.22/19 95.6 mg/L Yes- DWA
Uranium Jan.19/15 0.041 ug/L
Fluoride Jan.19/15 0.06 mg/L
Nitrite Annual range 0.003-0.003 mg/L
Nitrate Annual range 3.86 – 10.3 mg/L Yes -
Resampled *only for drinking water systems testing under Schedule 15.2; this includes large municipal non-
residential systems, small municipal non-residential systems, non-municipal seasonal residential
systems, large non-municipal non-residential systems, and small non-municipal non-residential
systems
Summary of lead testing under Schedule 15.1 during this reporting period
(applicable to the following drinking water systems; large municipal residential systems, small
municipal residential systems, and non-municipal year -round residential systems)
Location Type Number of
Samples
Range of Lead
Results
(min#) – (max #)
Number of
Exceedances
Plumbing 0
Distribution 4 Alk. = 232 - 250
pH = 7.41 - 7.58
0
Drinking-Water Systems Regulation O. Reg. 170/03
Drinking Water Systems Regulations
(PIBS 4435e01) February 2008 Page 5 of 6
Summary of Organic parameters sampled during this reporting period or the most
recent sample results
Parameter Sample
Date
Result
Value
Unit of
Measure
Exceedance
Alachlor Jan.19/15 0.02 ug/L
Aldicarb Jan.19/15 0.01 ug/L
Aldrin + Dieldrin Jan.19/15 0.01 ug/L
Atrazine + N-dealkylated metobolites Jan.19/15 0.01 ug/L
Azinphos-methyl Jan.19/15 0.02 ug/L
Bendiocarb Jan.19/15 0.01 ug/L
Benzene Jan.19/15 0.32 ug/L
Benzo(a)pyrene Jan.19/15 0.004 ug/L
Bromoxynil Jan.19/15 0.33 ug/L
Carbaryl Jan.19/15 0.01 ug/L
Carbofuran Jan.19/15 0.01 ug/L
Carbon Tetrachloride Jan.19/15 0.16 ug/L
Chlordane (Total) Jan.19/15 0.01 ug/L
Chlorpyrifos Jan.19/15 0.02 ug/L
Cyanazine Jan.19/15 0.03 ug/L
Diazinon Jan.19/15 0.02 ug/L
Dicamba Jan.19/15 0.20 ug/L
1,2-Dichlorobenzene Jan.19/15 0.41 ug/L
1,4-Dichlorobenzene Jan.19/15 0.36 ug/L
Dichlorodiphenyltrichloroethane (DDT) +
metabolites
Jan.19/15 0.01 ug/L
1,2-Dichloroethane Jan.19/15 0.35 ug/L
1,1-Dichloroethylene
(vinylidene chloride)
Jan.19/15 0.33 ug/L
Dichloromethane Jan.19/15 0.35 ug/L
2-4 Dichlorophenol Jan.19/15 0.15 ug/L
2,4-Dichlorophenoxy acetic acid (2,4-D) Jan.19/15 0.19 ug/L
Diclofop-methyl Jan.19/15 0.40 ug/L
Dimethoate Jan.19/15 0.03 ug/L
Dinoseb Jan.19/15 0.36 ug/L
Diquat Jan.19/15 1 ug/L
Diuron Jan.19/15 0.03 ug/L
Glyphosate Jan.19/15 1 ug/L
Heptachlor + Heptachlor Epoxide Jan.19/15 0.01 ug/L
Lindane (Total) Jan.19/15 0.01 ug/L
Malathion Jan.19/15 0.02 ug/L
Drinking-Water Systems Regulation O. Reg. 170/03
Drinking Water Systems Regulations
(PIBS 4435e01) February 2008 Page 6 of 6
Methoxychlor Jan.19/15 0.01 ug/L
Metolachlor Jan.19/15 0.01 ug/L
Metribuzin Jan.19/15 0.02 ug/L
Monochlorobenzene Jan.19/15 0.3 ug/L
Paraquat Jan.19/15 1 ug/L
Parathion Jan.19/15 0.02 ug/L
Pentachlorophenol Jan.19/15 0.15 ug/L
Phorate Jan.19/15 0.01 ug/L
Picloram Jan.19/15 1 ug/L
Polychlorinated Biphenyls(PCB) Jan.19/15 0.04 ug/L
Prometryne Jan.19/15 0.03 ug/L
Simazine Jan.19/15 0.01 ug/L
THM
(NOTE: show latest annual average) 2019 8.7 ug/L
Temephos Jan.19/15 0.01 ug/L
Terbufos Jan.19/15 0.01 ug/L
Tetrachloroethylene Jan.19/15 0.35 ug/L
2,3,4,6-Tetrachlorophenol Jan.19/15 0.20 ug/L
Triallate Jan.19/15 0.01 ug/L
Trichloroethylene Jan.19/15 0.44 ug/L
2,4,6-Trichlorophenol Jan.19/15 0.25 ug/L
2,4,5-Trichlorophenoxy acetic acid (2,4,5-T) Jan.19/15 0.22 ug/L
Trifluralin Jan.19/15 0.02 ug/L
Vinyl Chloride Jan.19/15 0.17 ug/L
HAA5 (Total Haloacetic Acids)
(NOTE: show latest annual average) 2019 5.3
<MDL
ug/L
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed
in Schedule 2 of Ontario Drinking Water Quality Standards.
Parameter Result Value Unit of Measure Date of Sample
2019 ANNUAL
SUMMARY REPORT FOR MUNICIPAL DRINKING WATER
SYSTEMS
Report
This report is a summary of water quality information for the Richmond Community
Water System, Water Works # 260074854, published in accordance with Schedule 22
of the Ontario’s Drinking Water Systems Regulation for the reporting period of January
1, 2019 to December 31, 2019. The Richmond Community Water System is categorized
as a Small Municipal Year Round Residential Drinking Water System, Class 2 water
treatment and Class 1 water distribution.
Who gets a copy of the Report:
The owner of the drinking – water system shall ensure that the following receive the
summary report no later than March 31 for the preceding calendar year;
• in the case of a drinking water system owned by a municipality, the members of
the Municipal Council;
• in the case of a drinking water system owned by a municipal service board
established under section 195 of the Municipal Act, 2001, the members of the
municipal service board; or
• in the case of a drinking water system owned by a corporation, the board of
directors of the corporation.
What must the Report contain?
The report must,
(a) list the requirements of the Act, the regulations, the system’s approval and any
order that the system failed to meet at any time during the period covered by
the report and specify the duration of the failure; and
(b) for each failure referred to in clause (a), describe the measures that were taken
to correct the failure.
The Richmond Community Water System complied with the following Drinking Water
Legislation;
• Safe Drinking Water Act
• O. Reg 170/03, O. Reg 128/04
• System Drinking Water Licence # 061-201, and Permit #061-202
What else must the report contain?
The report must also include the following information for the purposes of enabling the
owner of the system to assess the capability of the system to meet existing and planned
uses of the system:
• A summary of the quantities and flow rates of the water supplied during the
period covered by the report;
• A comparison of the summary referred to in paragraph 1 to the rated capacity and
flow rates approved in the system’s approval.
Attachments
• 2019 flows
Report Prepared by;
Ed Roloson, CMM III, CRS
Manager of Capital Projects – Water/Wastewater Operations
RICHMOND COMMUNITY WATER SYSTEM MONTHLY WATER CONSUMPTION
(m3)
Jan.Feb.March April May June July Aug.Sept.Oct.Nov.Dec.Totals
2019
East 444 423 488 513 596 603 449 432 375 390 366 402 5481
avg.daily 14 15 16 17 19 20 15 14 13 13 12 13
West 452 430 496 522 607 615 461 444 385 400 376 412 5600
avg. daily 15 15 16 17 20 21 15 14 13 13 13 13
2018
East 612 453 495 421 550 471 467 471 434 431 443 465 5713
avg.daily 18 16 16 14.0 18 15 15 15 14 13 15 15
West 620 464 508 435 565 483 480 482 445 441 452 475 5850
avg. daily 20 17 16 15 19 16 16 16 15 14 16 16
2017
East 390 313 379 354 429 420 563 538 423 538 559 687 5593
avg.daily 12.6 11.2 12.2 11.8 13.8 14 18.2 17.3 14.1 17.4 18.6 22
West 357 337 382 374 407 485 532 593 580 552 570 698 5867
avg. daily 11.5 12 12.3 12.5 13.1 16.2 17.2 19.1 19.3 17.8 19 22.5