HomeMy WebLinkAbout2018 - Bayham Water Distribution Systemr�
I/r Ontario Drinking -Water Systems Regulation O. Reg. 170/03
OPTIONAL ANNUAL REPORT TEMPLATE
Drinking -Water System Number: 260004748
Drinking -Water System Name: Bayham Distribution System
Drinking -Water System Owner: The Corporation of the Municipality of Bayham
Drinking -Water System Category: WD Large Municipal Residential
Period being reported: 2018
Complete if your Catemory is Large Municipal
Residential or Small Municipal Residential
Does your Drinking -Water System serve
more than 10,000 people? Yes [ ] No [ x ]
Is your annual report available to the public
at no charge on a web site on the Internet?
Yes [ x ] No[ ]
Location where Summary Report required
under O. Reg. 170/03 Schedule 22 will be
available for inspection.
1 Chatham St.
Port Burwell, Ont.
NOJ 1 TO
519-874-4761
Complete for all other Categories.
Number of Designated Facilities served:
N/A
Did you provide a copy of your annual
report to all Designated Facilities you
serve?
Yes [ ] No [ ]
Number of Interested Authorities you
report to:
Did you provide a copy of your annual
report to all Interested Authorities you
report to for each Designated Facility?
Yes [ ] No [ ]
Note: For the following tables below, additional rows or columns may be added or an
appendix may be attached to the report
List all Drinking -Water Systems (if any), which receive all of their drinking water from
ours stem:
Drinking Water System Name
L#:r:in:king Water System Number
N/A
Did you provide a copy of your annual report to all Drinking -Water System owners that
are connected to you and to whom you provide all of its drinking water?
Yes [ ] No[ ]
Drinking Water Systems Regulations Page 1 of 6
(PIBS 4435e01) February 2008
r�
I/r Ontario Drinking -Water Systems Regulation O. Reg. 170/03
Indicate how you notified system users that your annual report is available, and is free of
charge.
[ x ] Public access/notice via the web
[ x ] Public access/notice via Government Office
[ ] Public access/notice via a newspaper
[ x ] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[ x ] Public access/notice via other method _water
bills
Describe vour Drinking -Water Svstem
The Bayham water distribution system consists of various size transmission mains and
apparatuses including 81 fire hydrants, 100 main valves and 4 air release and 3 drain
chambers. The location of these are mainly located in the villages of Port Burwell and
Vienna. The estimated service population is 1590 with 798 fully metered service
connections. A booster pump station is located on the transmission main to Vienna.
This pump operates when the pressure drops to activate the pump which would
normally occur during fire flows or main line flushing.
List all water treatment chemicals used over this reporting period
No chemicals used as this report is a stand alone distribution system that receives
treated water.
Were any significant expenses incurred to?
[x ] Install required equipment
[x ] Repair required equipment
[ x ] Replace required equipment
Please provide a brief description and a breakdown of monetary expenses incurred
$660,990.28 --- regulatory operating expenses including purchase of water
Capital costs incurred for 2018 totaled $13,500 for air release valve /chamber works.
Drinking Water Systems Regulations Page 2 of 6
(PIBS 4435e01) February 2008
ram.
I/r Ontario Drinking -Water Systems Regulation O. Reg. 170/03
Provide details on the notices submitted in accordance with subsection 18(1) of the Safe
Drinking -Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to
Spills Action Centre
Incident
Date
Parameter
Result
Unit of
Measure
Corrective Action
Corrective
Action Date
Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03,
during this reporting period.
Number
Range of E.Coli
Range of Total
Number
Range of HPC
of
Or Fecal
Coliform
of HPC
Results
Samples
Results
Results
Samples
(min #)-(max #)
(min #)-(max #)
(min #)-(max #)
Raw
Treated
Distribution
157
0-0
0-0
157
<10 - >2000
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the
period covered by this Annual Report.
Number of
Range of Results
Grab
(min #)-(max #)
Samples
Turbidity
Chlorine
423
0.29 —1.73 (free)
Fluoride (If the
DWS provides
fluoridation)
NOTE: For continuous
monitors use 8760 as the
number of samples.
NOTE: Record the unit of measure if it is not milligrams per litre.
Drinking Water Systems Regulations
(PIBS 4435e01) February 2008
Page 3 of 6
ry
t);:>Ontarb Drinking -Water Systems Regulation O. Reg. 170/03
Summary of additional testing and sampling carried out in accordance with the
requirement of an approval, order or other legal instrument.
Date of legal instrument Parameter Date Sampled Result Unit of Measure
issued
Summary of Inorganic parameters tested during this reporting period or the most
recent sample results
Parameter
Sample Date
Result Value
Unit of Measure
Exceedance
Antimony
Arsenic
Barium
Boron
Cadmium
Chromium
*Lead
Mercury
Selenium
Sodium
Uranium
Fluoride
Nitrite
Nitrate
*only for drinking water systems testing under Schedule 15.2; this includes large municipal non-
residential systems, small municipal non-residential systems, non -municipal seasonal residential
systems, large non -municipal non-residential systems, and small non -municipal non-residential
systems
Drinking Water Systems Regulations Page 4 of 6
(PIBS 4435e01) February 2008
r�
t)�--:>Ontarb Drinking -Water Systems Regulation O. Reg. 170/03
Summary of lead testing under Schedule 15.1 during this reporting period
(applicable to the following drinking water systems; large municipal residential systems, small
municipal residential systems, and non -municipal year-round residential systems)
Location Type
Number of
Range of
Alkalinity Results
Number of
Samples
(min#) —(max #)
Exceedances
Plumbing
Distribution
8 pH, Lead and
Alk. 94-107mg/L
0
alkalinity
pH= 7.12-7.33
Lead 0.08-1.41
u /L
Summary of Organic parameters sampled during this reporting period or the most
recent sample results
Parameter
Sample
Date
Result
Value
Unit of
Measure
Exceedance
Alachlor
Aldicarb
Aldrin + Dieldrin
Atrazine + N-dealkylated metobolites
Azinphos-methyl
Bendiocarb
Benzene
Benzo(a)pyrene
Bromoxynil
Carbaryl
Carbofuran
Carbon Tetrachloride
Chlordane (Total)
Chlorpyrifos
Cyanazine
Diazinon
Dicamba
1,2-Dichlorobenzene
1,4-Dichlorobenzene
Dichlorodiphenyltrichloroethane (DDT) +
metabolites
1,2-Dichloroethane
1,1-Dichloroethylene
vin lidene chloride
Dichloromethane
2-4 Dichlorophenol
2,4-Dichlorophenoxy acetic acid (2,4-D)
Drinking Water Systems Regulations Page 5 of 6
(PIBS 4435e01) February 2008
r�
. r Ontario Drinking -Water Systems Regulation O. Reg. 170/03
Diclofop-methyl
Dimethoate
Dinoseb
Diquat
Diuron
Glyphosate
HAAs (Total Haloacetic Acids)
(NOTE: show latest annual average)
2018
26.3
ug/L
Heptachlor + Heptachlor Epoxide
Lindane (Total)
Malathion
Methoxychlor
Metolachlor
Metribuzin
Monochlorobenzene
Paraquat
Parathion
Pentachlorophenol
Phorate
Picloram
Polychlorinated Biphenyls(PCB)
Prometryne
Simazine
THM
(NOTE: show latest annual average)
2018
55.5
ug/L
Temephos
Terbufos
Tetrachloroethylene
2,3,4,6-Tetrachlorophenol
Triallate
Trichloroethylene
2,4,6-Trichlo roph en o l
2,4,5-Trichlorophenoxy acetic acid (2,4,5-T)
Trifluralin
Vinyl Chloride
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed
in Schedule 2 of Ontario Drinking Water Quality Standards.
Parameter
Result Value
Unit of Measure
Date of Sample
THM
58
ug/L
Jan.8/2018
THM
35
ug/L
April 3/2018
THM
58
ug/L
Jul 10/2018
THM
71
ug/L
Oct. 1/2018
Drinking Water Systems Regulations Page 6 of 6
(PIBS 4435e01) February 2008
2018 ANNUAL
SUMMARY REPORT FOR MUNICIPAL WATER SYSTEMS
Report
This report is a summary of water quality information for the Bayham Water
Distribution System, Water Works # 260004748, published in accordance with
Schedule 22 of the Ontario's Drinking Water Systems Regulation for the reporting
period of January 1, 2018 to December 31, 2018. The Bayham Water Distribution
System is categorized as a Class I, Large Municipal Residential Drinking Water System.
Who gets a copy of the Report:
The owner of the drinking — water system shall ensure that the following receive the
summary report no later than March 31 for the preceding calendar year;
• in the case of a drinking water system owned by a municipality, the members of
the Municipal Council;
in the case of a drinking water system owned by a municipal service board
established under section 195 of the Municipal Act, 2001, the members of the
municipal service board; or
• in the case of a drinking water system owned by a corporation, the board of
directors of the corporation.
What must the Report contain?
The report must,
(a) list the requirements of the Act, the regulations, the system's approval and any
order that the system failed to meet at any time during the period covered by
the report and specify the duration of the failure; and
(b) for each failure referred to in clause (a), describe the measures that were taken
to correct the failure.
The Bayham Water Distribution System complied with the following Drinking Water
Legislation;
• Safe Drinking Water Act
• O. Reg 170/03, O. Reg 128/04
• System Drinking Water Licence # 061-101, and Permit 9061-102
Note: MOE inspection conducted on January 10, 2019 (report pending)
What else must the report contain?
The report must also include the following information for the purposes of enabling the
owner of the system to assess the capability of the system to meet existing and planned
uses of the system:
A summary of the quantities and flow rates of the water supplied during the
period covered by the report;
A comparison of the summary referred to in paragraph 1 to the rated capacity and
flow rates approved in the system's approval.
Attachments
• 2018 flows
Report Prepared by;
Ed Roloson, CMM III, CRS
Manager of Capital Projects - Water/Wastewater Operations
Overall Responsible Operator ( ORO )
MUNICIPALITY OF BAYHAM MONTHLY WATER CONSUMPTION (m3)
Jan. Feb. March April May June July Aug. Sept. Oct. Nov. Dec. Totals
2018
Pt. Bu rwel I
6960
avg.daily
225
Vienna
4353
avg. daily
140
Lake View
11,690
avg. daily
377
2017
Pt. B u rwel l
5581
avg.daily
180
Vienna
4088
avg. daily
132
Lake View
10,141
avg. daily
327
5028
6639
5942
4760
8854
9387
9836
8530
6960
5130
7202
85,228
180
214
198
154
295
303
318
284
225
171
232
4229
5670
4657
4673
5001
5060
4122
4645
4353
3640
4639
55,042
151
183
155
151
167
163
133
155
140
121
150
9,773
12,404
10,599
12,938
13,404
14,197
15,221
13,862
12,142
8,755
11,776
146,761
349
413
354
417
447
458
491
462
392
292
380
4943
5221
6924
6874
9080
10879
10002
7178
6778
5408
5708
84,576
176
168
231
222
303
351
323
239
219
180
184
3529
3931
4059
4170
3826
4549
4749
4428
4764
4340
4571
51,004
126
127
135
134
127
147
153
148
154
145
147
8,987
10,512
11,589
12,629
13,239
16,001
15,872
13,459
11,568
10,532
11,030
145,559
321
339
386
408
441
516
512
449
373
351
356